INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ BC160NT305...

Podobné dokumenty
PS-BC-0010 PS-BC-0010-Au NS-BC-0010 NS-BC-0010-Au

BC160NT BC160NT406...

CIRCUIT BREAKER, SWITCH-DISCONNECTOR BC160NT305...

BH40NE OD-BHD-KS02. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ BC160NT305...

SP-BC-... SV-BC-... Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

SWITCHING UNIT SPÍNACÍ BLOK BL1600SE305 BL1600SE305 OD-BL-KS02 OD-BL-MS01

SWITCH-DISCONNECTOR ODPÍNAČ BL1000SE V BL1000SE V OD-BL-KS02 OD-BL-MS01

BH40NE OD-BHD-KS02. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

BD250NE305 BD250SE305

BD250NE305 BD250SE305

Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

BH630NE305 BH630SE305

Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

ENGLISH ČESKY INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ EMPTY ENCLOSURE ROZVODNICOVÁ SKŘÍŇ RNG, RZG, RZV a Z00

BH630NE V OD-BHD-KS02. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

BD250NE305 BD250SE305

BH630NE305 BH630SE305

SE-BD-...-M TV9 SE-BH-...-MTV9

SE-BD SE-BH

N>Nmax ON/OFF ON OFF ON,OFF,ON/OFF ON/OFF OFF Nmax =15. t=6sec. MIR (N) (N) Rz 11 L1 (AC 230 V) L1 (AC 230 V) OD-MIR-BK OFF (OFF)

BD250NE V. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

BH630NE V OD-BHD-KS02. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

BH630NE300 BH630SE300

BD250NE300 BD250SE300

PS-BHD-0010 PS-BHD-0020

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ SJB-25E-3N-MZS

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ COMBINED LIGHTNING CURRENT AND SURGE VOLTAGE ARRESTER SJBC-25E-3-MZS

MCR-MA-001-UNI MCR-MA-003-UNI

SVBC-12,5-4-MZ SVBC-12,5-4-MZS

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ BC160NT305...

SVC MZ SVC MZS


ZES-4. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ FH00-1

BD250NE300 BD250SE300

BD250NE305 BD250SE305

SVM-440-Z SVM-440-ZS

SWITCHING UNIT SPÍNACÍ BLOK BL1600SE305 BL1600SE305 OD-BL-KS02 OD-BL-MS01

BH100NE OD-BHD-KS02. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

BD40NE OD-BHD-KS02. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

BH630NE305 BH630SE305

SVM-440-ZS SVM-440-Z

BC160NT BC160NT406...

SVC MZ SVC MZS

MMR-X3-001-A230. Návod k použitiu ПО-РУССКИ PO POLSKU DEUTSCH SLOVENSKY

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ BH40NE305...

SWITCHING UNIT SPÍNACÍ BLOK BL1000SE305 BL1000SE305 OD-BL-KS02 OD-BL-MS01

SWITCH-DISCONNECTOR ODPÍNAČ BL1600SE V BL1600SE V OD-BL-KS02 OD-BL-MS01

BL1600SE305 INSTRUCTIONS FOR USE, NÁVOD K POU ITÍ ENGLISH ÈESKY SWITCHING UNIT SPÍNACÍ BLOK BL1600SE305 OD-BL-KS02 OD-BL-MS01

Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

SWITCH-DISCONNECTOR ODPÍNAČ BL1000SE V BL1000SE V OD-BL-KS02 OD-BL-MS01

BD250NE V. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

TN-S. max. 25A gl/gg TN-C. max. 25A gl/gg

RPI X230-S... RPI X230-S... RPI UNI-S...

OUT CIRCUIT DIAGRAM SCHÉMA ZAPOJENÍ. Remote signalling Dálková signalizace 11 S 12 CONNECTION ZAPOJENÍ TN-S TN-C b Z00 N PE. max.

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ

BH630NE305 BH630SE305

RZB INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ ENGLISH ČESKY EMPTY ENCLOSURE ROZVODNICOVÁ SKŘÍŇ

BD250NE V OD-BHD-KS02. Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

BH630NE305 BH630SE305

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ BD250NE V

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ FH00-3

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ ZO-BD

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ FSD00-33K-F.

BD250NE300 BD250SE300

RP-BH-CK30 RP-BH-CK31

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ BD250NE V

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ SVD-253-1N-MZS

FH1-3 INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ ENGLISH ESKY FUSE SWITCH-DISCONNECTOR POJISTKOVÝ ODPÍNA

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ FH2-3

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ FSD00-3.D-F.

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ MCR-TK-001-UNI A1 A2 MCR-TK

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ MMR-T2-200-A230

SB-BL Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only.

2 OVERVIEW AFD-16-1N-M3 AFD-16-1N-M2 PŘEHLED Z00 OLE, OLI LTK AFD-16-1N-M3 OLE, OLI 1 N 2 N

SWITCHING UNIT SPÍNACÍ BLOK BL1000SE320

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ AFD-16-1N-..

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ MMR-U3-001-A230 L1 N L2 L3 MMR-U3

INSTRUCTIONS FOR USE, NÁVOD K POU ITÍ FR00-3D/F.

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ NP66-..., NP55-...

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ SP-BL-... SV-BL-...

ARION WL NÁVOD K POUŽITÍ NÁVOD K POUŽITIU ИНСТРУКЦИЯ ПО ЭКСПЛУАТАЦИИ INSTRUCTIONS FOR USE ČESKY SLOVENSKY ПО-РУССКИ ENGLISH

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ MMR-X3-001-A230 L1 N L2 L3 MMR-X3


STAVEBNÍ PŘIPRAVENOST GILOTINA VLO DIMENSIONAL SHEET VLO MASSBLATT VERTIKALER BESCHLAG VLO МОНТАЖ МЕТАЛЛОКОНСТРУКЦИИ ВОРОТ СИСТЕМЫ ГИЛЬОТИНА ВЛО

INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ

BL1600SE320 INSTRUCTIONS FOR USE, NÁVOD K POU ITÍ ENGLISH ÈESKY SWITCHING UNIT SPÍNACÍ BLOK

ATMOS ACD01 ELEKTROINSTALACE

1-AYKY. Instalační kabely s Al jádrem. Standard TP-KK-133/01, PNE Konstrukce. Použití. Vlastnosti. Installation cables with Al conductor

Instalační kabely s Cu jádrem

RN-PNS. Pre-wired consumer unit IP40 Rozváděč IP40 Zapojený rozvádzač IP40. Mounting instructions Montážní návod Montážne inštrukcie

2 Izolace PVC. PVC insulation

UNZ-10T UNZR-10T INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ ENGLISH ČESKY POWER SUPPLY NAPÁJECÍ ZDROJ

Instalační kabely s Cu jádrem

STAVEBNÍ PŘIPRAVENOST GILOTINA VL DIMENSIONAL SHEET VL MASSBLATT VERTIKALER BESCHLAG VL МОНТАЖ МЕТАЛЛОКОНСТРУКЦИИ ВОРОТ СИСТЕМЫ ГИЛЬОТИНА ВЛ

3 Výplňový obal. 4 Plášť PE. Bedding

3 Výplňový obal. 4 Plášť PE. Bedding

Transkript:

ENGLISH ESKY INSTRUCTIONS FOR USE, NÁVOD K POUŽITÍ CIRCUIT BREAKER, SWITCH-DISCONNECTOR JISTI A ODPÍNA BC6NT35... BC6NT35... OD-BC-KS2 OD-BC-MS Installation, service and maintenance of the electrical equipment may be carried out by an authorized person only. Montáž, obsluhu a údržbu smí provád t jen osoba s odpovídající elektrotechnickou kvalifikací. OEZ s.r.o., Šedivská 339, 56 5 Letohrad, Czech Republic, www.oez.cz 998i Z

2 Setting of releases Nastavení spouští BC6... 25 6 I R 5 I=nxI i n 6-L TEST 6-N TEST CHARACTERISTIC CHARAKTERISTIKA L Category A I n= 6A I R=In I= 4 xi i n CHARACTERISTIC CHARAKTERISTIKA N Category A I n= 6A 5 Ii=nxIn 6-D TEST 6-V TEST 25 6 I n= 6A I e= 6A CHARACTERISTIC CHARAKTERISTIKA D 5 I R [A] Category A Ii=nxIn SWITCH - DISCONNECTOR ODPÍNA V 6-M TEST CHARACTERISTIC CHARAKTERISTIKA M 25 6 I R [A] Category A I n= 6 A Ii= xin -2-998i Z

3 MOUNTING MONTÁŽ,5 Nm OD-BC-MS 2x... M3x3 PS-BC- PS-BC- =switched on sepnuto )* 6 or, nebo - 6 PS-BC-... Auxiliary switch Pomocný spína NS-BC-... Signal switch Náv stní spína =switched off rozepnuto State of circuit-breaker 2)*.2.4.2.4.Y.Y Auxiliary releases Pomocné spoušt Stav jisti e...y2.y2 SV-BC-... SP-BC-... PS-BC- SP-BC SV-BC TEST -3-998i Z

4.Y2 D2.Y D SP-BC-....Y2.Y C2 C SV-BC-.....NS-BC-.2.4. 2. 3. 4. 5. 6..PS-BC- 2.PS-BC- 3.PS-BC- 4.PS-BC- 5.PS-BC- 6.PS-BC-.2.4 2.2 2.4 3.2 3.4 4.2 4.4 5.2 5.4 6.2 6.4-4- 998i Z

5 FIXED DESIGN, FRONT CONNECTION PEVNÉ PROVEDENÍ, P EDNÍ P ÍVOD 8 2,5 2 2 68,5 DRILLING DIAGRAM VRTACÍ PLÁN 25 38 25 25 75 2 7 8 25 25. 3. 4. 5. 2,5 6mm2 Al, Cu... 4 Nm 4 25 95mm2Al... 6 Nm 4 25 95mm2Cu... 8 Nm 4 2. -5-998i Z

6 SEALING PLOMBOVÁNÍ BC6... 7 OPERATING POSITIONS PRACOVNÍ POLOHY BC6... 25 9 9 9-6- 998i Z

8 MINIMUM DEIONIZATION SPACE WITHOUT EARTHED METALLIC CONSTRUCTIONS MINIMÁLNÍ DEIONIZA NÍ PROSTOR BEZ KOVOVÝCH UZEMN NÝCH KONSTRUKCÍ C=2 H=3 B=75 B=75 B= C=2 OD-BC-KS42 x OD-BC-KS2 2x E=7 ) G=4 BC6... F= 2) G= A A - minimum distance between the circuit breaker and bare wall (this is valid for insulated conductors, cables, flexi bars or rear connection) - minimální vzdálenost mezi jisti em a neizolovanou uzemn nou st nou (platí pro izolované vodi e, kabely, flexibary nebo zadní p ívod) - minimum length of insulation of bare conductors (with use of insulating barriers OD-BC-KS2 from 5 mm to max. mm, possibly with additional insulation of conductors above the barriers to A level) - minimální délka izolace holých vodi (použitím izola ních p epážek OD-BC-KS2 od 5 mm do max. mm, p ípadn dopl kovou izolací vodi nad p epážkami minimáln na hodnotu A) A2 -minimum distance between the circuit breaker and bare wall (this is valid for bare conductors and busbars),... between the conductor and busbar,... between two circuit breakers installed vertically above each other,... between bare leads of two circuit breakers above each other - minimální vzdálenost mezi jisti em a neizolovanou uzemn nou st nou (platí pro neizolované vodi e a sb rnice),... mezi jisti em a sb rnicí,... mezi dv mi jisti i umíst nými vertikáln nad sebou,... mezi neizolovanými p ívody dvou jisti nad sebou C,D,E,F,G-minimum distance between circuit breaker and bare earthed wall - minimální vzdálenost mezi jisti em a neizolovanou uzemn nou st nou H - minimum distance between bare conductors - minimální vzdálenost mezi neizolovanými vodi i ) U n > 45 V a.c. 2) n 45 V a.c. -7-998i Z

U=23 V AC U=45 V AC U=5 V AC U=69 V AC Icu = 4 ka Icu = 25 ka Icu = 2 ka Icu = 6 ka A A A2 H 5 mm mm 5 mm 3 mm 9 Only materials which have low adverse environmental impact and which do not contain dangerous substances as specified in ROHS directive have been used in the product. Ve výrobku jsou použity materiály s nízkým negativním dopadem na životní prost edí, které neobsahují zakázané nebezpe né látky dle ROHS. -8-998i Z

SLOVENSKY DEUTSCH ESPAÑOL PO POLSKU ПО-РУССКИ BC6NT35... - - 998i Z

Gebrauchsanweisung DEUTSCH Kompaktleistungsschalter - BC6NT35... Die Montage, die Bedienung und Instandhaltung kann nur der Arbeiter mit der entsprechenden elektrotechnischen Qualifikation verrichten. 2 Einstellung des Auslösers Charakteristik L Lasttrennschalter V 3 Montage ()-(6) PS-BC-... Hilfsschalter () PS-BC-... Meldeschalter () SP-BC-..., SV-BC-... Hilfsauslöser )* = ein = aus 2)* Zustand des Leistungsschalters 4 Leistungsschalter BC6 mit Zubehör 5 Feste Ausführung Vorderanschluss Bohrplan 6 Plombieren 7 Gebrauchslagen 8 Mindestanschlussraum ohne geerdeten Metallkonstruktionen A - Mindestabstand zwischen dem Leistungsschalter und einer nicht isolierten geerdeten Wand (es gilt für nicht isolierte Leiter, Kabel, Flexibare oder den rückseitigen Anschluss) A - Mindestlänge der Isolation von blanken Leitern (wird von 5 mm bis max. mm durch isolierende Trennwände OD-BC-KS2, bzw. durch Isolierstoffabdeckung der Leiter über den isolierenden Trennwänden auf Mindestwert A realisiert) A2 - Mindestabstand zwischen dem Leistungsschalter und einer nicht isolierten geerdeten Wand (es gilt für blanke Leiter und Sammelschienen),... zwischen Leistungsschalter und Sammelschiene... zwischen zwei gegenseitig vertikal übereinander eingebauten Leistungsschaltern... zwischen blanken Anschlüssen von zwei gegenseitig übereinander eingebauten Leistungsschaltern C, D, E, F, G - Mindestabstand zwischen dem Leistungsschalter und einer nicht isolierten geerdeten Wand H - Mindestabstand zwischen blanken Leitern 9 Für das Erzeugnis werden Stoffe mit niedrigen negativen Umweltauswirkungen angewandt, die keine verbotenen gefährlichen Stoffe nach ROHS enthalten. - 2-998i Z

Instrucciones de uso ESPAÑOL Interruptor de protección compactos - BC6NT35... El montaje, servicio y mantenimiento puede realizar únicamente la persona con la cualificación electrotécnica correspondiente. 2 Ajuste del disparador (de la bobina) Característica L Interruptor separador V 3 Montaje ()-(6) PS-BC-... Contactor auxiliar () PS-BC-... Interruptor de señal () SP-BC-..., SV-BC-... Auxiliares de disparo )* = conectado = desconectado 2)* Estado del disyuntor 4 Disyuntor BC6 con accesorios 5 Versión fija Conexión frontal Diagrama de taladrado 6 Selladura 7 Posiciones de operación 8 Área mínima de desionización sin construcciones metálicas con toma de tierra A - La distancia mínima entre el disyuntor y la pared sin aislamiento con toma de tierra (aplicable a conductores con aislamiento, cables, barras colectoras de láminas o conexión trasera) A - Longitud mínima del aislamiento de conductores sin aislamiento (uso de barreras de aislamiento OD-BC-KS2 desde 5 mm hasta mm máx. o aislamineto de conductores auxiliar encima de barreras, mínimo el valor A). A2 - La distancia mínima entre el disyuntor y la pared sin aislamiento con toma de tierra (aplicable a conductores sin aislamiento y barras colectoras) entre el disyuntor y la barra colectora entre dos disyuntores situados horizontalmente uno encima del otro... entre los cables sin aislamiento de dos disyuntores uno encima del otro C, D, E, F, G - La distancia mínima entre el disyuntor y la pared sin aislamiento con toma de tierra H - La distancia mínima entre conductores sin aislamiento 9 En el producto están usados los materiales que tienen incidencia negativa baja al medio ambiente, que no incluyen las materias peligrosas prohibidas según ROHS. - 3-998i Z

Instrukcja obsługi PO POLSKU Wyłącznik kompaktowy - BC6NT35... Montaż, obsługę i konserwację wykonywać może wyłącznie odpowiednio wykwalifikowana osoby z branży elektrotechnicznej. 2 Ustawienie przekaźnika Charakterystyka L Rozłącznik V 3 Montaż ()-(6) PS-BC-... Wyłącznik pomocniczy () PS-BC-... Wyłącznik sygnalizacyjny () SP-BC-..., SV-BC-... Wyzwalacze pomocnicze )* = włączone = rozłączone 2)* Stan wyłącznika 4 Wyłącznik BC6 z akcesoriami 5 Wykonanie stałe Przyłacza przednie Plan wiercenia 6 Plombowanie 7 Pozycja pracy 8 Minimalna wartośc strefy dejonizacyjnej bez uziemionej metalowej konstrukcji A - Minimalny odstęp między wyłącznikiem a scianą (zależnie od przyłaczy, kabli, przyłacza bocznego) A - Minimalna długosc izolacji na odsłoniętych złączach (z użyciem przegród miedzyfazowych OD-BC-KS2 od 5 mm do mm, możliwe z dodatkową izolacją złączy po obu stronach barier do poziomu A) A2 - Minimalny odstęp między wyłącznikiem a scianą (zalezny od złączy i szyn), między wyłącznikiem a szyną instalujemy pionowo między dwoma wyłącznikami pomiędzy odsłonientymi przewodami dwuch wyłącznik umieszczonych obok siebie C, D, E, F, G - Minimalny odstęp między wyłącznikiem a scianą H - Minimalny odstęp pomiędzy przyłaczami 9 W wyrobie zastosowane zostały materiały z niskim negatywnym oddziaływaniem na środowisko naturalne, które nie zawierają zakazanych niebezpiecznych substancji zgodnie z ROHS. - 4-998i Z

Инструкция по эксплуатации ПО-РУССКИ Компактный автоматический выключатель - BC6NT35... Установку, обслуживание и уход может проводить только лицо с соответствующей электротехнической квалификацией. 2 Настройка расцепителей Xарактеристика L Разъединитель нагрузки V 3 Установка ()-(6) PS-BC-... Вспомогательный выключатель () PS-BC-... Сигнальный выключатель () SP-BC-..., SV-BC-... Вспомогательные расцепители )* = включен = разомкнутый 2)* Состояние автоматического выключателя 4 Автоматический выключатель BC6 с принадлежностями 5 Стационарное исполнение Передний подвод План сверления 6 Пломбирование 7 Рабочие положения 8 Мин. деионизационное пространство без металлических заземленных конструкций A - Минимальное расстояние между автоматическим выключателем и неизолированной заземленной стенкой (действительно для изолированных проводников, кабелей, гибких шин или заднего подвода) A - Минимальная длина изоляции неизолированных проводников (используя изоляционные перегородки OD-BC-KS2 от 5 mm до максимум mm или дополнительную изоляцию проводников над перегородками как минимум на величину А) A2 - Минимальное расстояние между автоматическим выключателем и неизолированной заземленной стенкой (действительно для неизолированных проводников и шин), между автоматическим выключателем и шиной между двумя автоматическими выключателями, размещенными вертикально друг над другом между неизолированными вводами двух автоматических выключателей друг над другом C, D, E, F, G - Mинимальное расстояние между автоматическим выключателем и неизолированной заземленной стенкой H - Минимальное расстояние между неизолированными проводниками 9 В изделии применены материалы с малым негативным влиянием на окружающую среду, которые не содержат запрещенные опасные вещества, указанные в директиве ROHS. - 5-998i Z

Návod k použitiu SLOVENSKY Istič MCCB - BC6NT35... Montáž, obsluhu a údržbu môže vykonávať iba osoba s odpovedajúcou elektrotechnickou kvalifikáciou. 2 Nastavenie spúští Charakteristika L Odpínač V 3 Montáž ()-(6) PS-BC-... Pomocný spínač () PS-BC-... Návestný spínač () SP-BC-..., SV-BC-... Pomocné spúšte )* = zopnuté = rozopnuté 2)* Stav ističa 4 Istič BC6 s príslušenstvom 5 Pevné prevedenie Predný prívod Vŕtací plán 6 Plombovanie 7 Pracovné polohy 8 Minimálny deionizačný priestor bez kovových uzemnených konštrukcií A - Minimálna vzdialenosť medzi ističom a neizolovanou uzemnenou stenou (platí pre izolované vodiče, káble, flexibary alebo zadný prívod) A - Minimálna dĺžka izolácie holých vodičov (použitím izolačných prepážok OD-BC-KS2 od 5 mm do max. mm, prípadne doplnkovou izoláciou vodičov nad prepážkami minimálne na hodnotu A) A2 - Minimálna vzdialenosť medzi ističom a neizolovanou uzemnenou stenou (platí pre neizolované vodiče a zbernice),... medzi ističom a zbernicou... Medzi dvoma ističmi umiestnenými vertikálne nad sebou... medzi neizolovanými prívodmi dvoch ističov nad sebou C, D, E, F, G - Minimálna vzdialenosť medzi ističom a neizolovanou uzemnenou stenou H - Minimálna vzdialenosť medzi neizolovanými vodičmi 9 Vo výrobku sú použite materiály s nízkym negatívnym dopadom na životné prostredie, ktoré neobsahuje zakázané latky podľa ROHS - 6-998i Z

DRILLING DIAGRAM VRTACÍ PLÁN : 25 25 25 998i Z