- (06-57) - ADDRESS CVERSI TABLE FOR MANUAL SETTING In the case of a multiple refrigerant system, each refrigerant system should be set an exclusive refrigerant. Conversion table of refrigerant and rotary switch are shown in the table below. Do not use a nonexistent switch combination. Rotary SW is formed with the Hexadecimal notation. conversion table (Outdoor unit) ( : "0", : "0" - - - Factory ) 0 0 0 1 0 1 2 0 2 3 0 3 4 0 4 5 0 5 6 0 6 7 0 7 8 0 8 9 0 9 10 0 A 11 0 B 12 0 C 13 0 D 14 0 E 15 0 F 16 1 0 17 1 1 18 1 2 19 1 3 20 1 4 21 1 5 22 1 6 23 1 7 24 1 8 25 1 9 26 1 A 27 1 B 28 1 C 29 1 D 30 1 E 31 1 F 32 2 0 33 2 1 34 2 2 35 2 3 36 2 4 37 2 5 38 2 6 39 2 7 40 2 8 41 2 9 42 2 A 43 2 B 44 2 C 45 2 D 46 2 E 47 2 F 48 3 0 49 3 1 50 3 2 51 3 3 52 3 4 53 3 5 54 3 6 55 3 7 56 3 8 57 3 9 58 3 A 59 3 B 60 3 C 61 3 D 62 3 E 63 3 F 64 4 0 65 4 1 66 4 2 67 4 3 68 4 4 69 4 5 70 4 6 71 4 7 72 4 8 73 4 9 74 4 A 75 4 B 76 4 C 77 4 D 78 4 E 79 4 F 80 5 0 81 5 1 82 5 2 83 5 3 84 5 4 85 5 5 86 5 6 87 5 7 88 5 8 89 5 9 90 5 A 91 5 B 92 5 C 93 5 D 94 5 E 95 5 F 96 6 0 97 6 1 98 6 2 99 6 3 Example : 30 : Set Rotary to "1" and to "E"
- (06-58) - conversion table ( unit) 1 PCB Type A : Compact Cassette Type Cassette Type Compact Duct Type Low Static Pressure Duct Type Duct Type Floor / Ceiling Type Ceiling Type Wall Mounted Type Ceiling Wall Type ( : "0", : "0" - - - Factory ) 0 0 0 1 0 1 2 0 2 3 0 3 4 0 4 5 0 5 6 0 6 7 0 7 8 0 8 9 0 9 10 0 A 11 0 B 12 0 C 13 0 D 14 0 E 15 0 F 16 1 0 17 1 1 18 1 2 19 1 3 20 1 4 21 1 5 22 1 6 23 1 7 24 1 8 25 1 9 26 1 A 27 1 B 28 1 C 29 1 D 30 1 E 31 1 F 32 2 0 33 2 1 34 2 2 35 2 3 36 2 4 37 2 5 38 2 6 39 2 7 40 2 8 41 2 9 42 2 A 43 2 B 44 2 C 45 2 D 46 2 E 47 2 F 48 3 0 49 3 1 50 3 2 51 3 3 52 3 4 53 3 5 54 3 6 55 3 7 56 3 8 57 3 9 58 3 A 59 3 B 60 3 C 61 3 D 62 3 E 63 3 F 64 4 0 65 4 1 66 4 2 67 4 3 68 4 4 69 4 5 70 4 6 71 4 7 72 4 8 73 4 9 74 4 A 75 4 B 76 4 C 77 4 D 78 4 E 79 4 F Example : 30 : Set Rotary to "1" and to "E" 80 5 0 81 5 1 82 5 2 83 5 3 84 5 4 85 5 5 86 5 6 87 5 7 88 5 8 89 5 9 90 5 A 91 5 B 92 5 C 93 5 D 94 5 E 95 5 F 96 6 0 97 6 1 98 6 2 99 6 3
conversion table ( unit) 2 PCB Type B : Compact Wall Mounted Type (Comfort model) 5-1 5-2 5-3 0 OFF OFF OFF 0 1 OFF OFF OFF 1 2 OFF OFF OFF 2 3 OFF OFF OFF 3 4 OFF OFF OFF 4 5 OFF OFF OFF 5 6 OFF OFF OFF 6 7 OFF OFF OFF 7 8 OFF OFF OFF 8 9 OFF OFF OFF 9 10 OFF OFF OFF A 11 OFF OFF OFF B 12 OFF OFF OFF C 13 OFF OFF OFF D 14 OFF OFF OFF E 15 OFF OFF OFF F 16 OFF OFF 0 17 OFF OFF 1 18 OFF OFF 2 19 OFF OFF 3 20 OFF OFF 4 21 OFF OFF 5 22 OFF OFF 6 23 OFF OFF 7 24 OFF OFF 8 AS*E07, AS*E09, AS*E12, AS*E14 Rotary SW 5-1 5-2 25 OFF OFF 9 26 OFF OFF A 27 OFF OFF B 28 OFF OFF C 29 OFF OFF D 30 OFF OFF E 31 OFF OFF F 32 OFF OFF 0 33 OFF OFF 1 34 OFF OFF 2 35 OFF OFF 3 36 OFF OFF 4 37 OFF OFF 5 38 OFF OFF 6 39 OFF OFF 7 40 OFF OFF 8 41 OFF OFF 9 42 OFF OFF A 43 OFF OFF B 44 OFF OFF C 45 OFF OFF D 46 OFF OFF E 47 OFF OFF F 48 OFF 0 49 OFF 1 (SW5-1: "OFF", SW5-2: "OFF", SW5-3: "OFF",: "0" --- Factory ) 5-3 Rotary SW 5-1 5-2 5-3 Rotary SW 50 OFF 2 51 OFF 3 52 OFF 4 53 OFF 5 54 OFF 6 55 OFF 7 56 OFF 8 57 OFF 9 58 OFF A 59 OFF B 60 OFF C 61 OFF D 62 OFF E 63 OFF F 64 OFF OFF 0 65 OFF OFF 1 66 OFF OFF 2 67 OFF OFF 3 68 OFF OFF 4 69 OFF OFF 5 70 OFF OFF 6 71 OFF OFF 7 72 OFF OFF 8 73 OFF OFF 9 74 OFF OFF A 5-1 5-2 75 OFF OFF B 76 OFF OFF C 77 OFF OFF D 78 OFF OFF E 79 OFF OFF F 80 OFF 0 81 OFF 1 82 OFF 2 83 OFF 3 84 OFF 4 85 OFF 5 86 OFF 6 87 OFF 7 88 OFF 8 89 OFF 9 90 OFF A 91 OFF B 92 OFF C 93 OFF D 94 OFF E 95 OFF F 96 OFF 0 97 OFF 1 98 OFF 2 99 OFF 3 Example : 30 : Set 5-1 to "",5-2 and 5-3 to "OFF", Rotary to "E" 5-3 Rotary SW 1 2 3 4 5 - (06-59) -
unit Each indoor unit in a refrigerant system should be set an exclusive indoor unit with rotary switches or DIP switches. Conversion table of indoor unit and rotary switch are shown in the table below. Do not use a nonexistent switch combination. Rotary SW is formed with the Hexadecimal notation unit conversion table 1 PCB Type A : Compact Cassette Type Cassette Type Compact Duct Type Low Static Pressure Duct Type Duct Type Floor / Ceiling Type Ceiling Type Wall Mounted Type Ceiling Wall Type ( : "0", : "0" - - - Factory ) unit unit unit unit unit 0 0 0 1 0 1 2 0 2 3 0 3 4 0 4 5 0 5 6 0 6 7 0 7 8 0 8 9 0 9 10 0 A 11 0 B 12 0 C 13 0 D 14 0 E 15 0 F 16 1 0 17 1 1 18 1 2 19 1 3 20 1 4 21 1 5 22 1 6 23 1 7 24 1 8 25 1 9 26 1 A 27 1 B 28 1 C 29 1 D 30 1 E 31 1 F 32 2 0 33 2 1 34 2 2 35 2 3 36 2 4 37 2 5 38 2 6 Example : unit 47 : Set Rotary to "2" and to "F" 39 2 7 40 2 8 41 2 9 42 2 A 43 2 B 44 2 C 45 2 D 46 2 E 47 2 F 48 3 0 49 3 1 50 3 2 51 3 3 52 3 4 53 3 5 54 3 6 55 3 7 56 3 8 57 3 9 58 3 A 59 3 B 60 3 C 61 3 D 62 3 E 63 3 F - (06-60) -
unit conversion table unit 2 PCB Type B : Compact Wall Mounted Type (Comfort model) 4-1 4-2 Rotary SW 0 OFF OFF 0 1 OFF OFF 1 2 OFF OFF 2 3 OFF OFF 3 4 OFF OFF 4 5 OFF OFF 5 6 OFF OFF 6 7 OFF OFF 7 8 OFF OFF 8 9 OFF OFF 9 10 OFF OFF A 11 OFF OFF B 12 OFF OFF C 13 OFF OFF D 14 OFF OFF E 15 OFF OFF F AS*E07, AS*E09, AS*E12, AS*E14 (SW4-1: "OFF", SW4-2: "OFF", : "0" --- Factory ) unit 4-1 4-2 Rotary SW 16 OFF 0 17 OFF 1 18 OFF 2 19 OFF 3 20 OFF 4 21 OFF 5 22 OFF 6 23 OFF 7 24 OFF 8 25 OFF 9 26 OFF A 27 OFF B 28 OFF C 29 OFF D 30 OFF E 31 OFF F unit 4-1 4-2 Rotary SW 32 OFF 0 33 OFF 1 34 OFF 2 35 OFF 3 36 OFF 4 37 OFF 5 38 OFF 6 39 OFF 7 40 OFF 8 41 OFF 9 42 OFF A 43 OFF B 44 OFF C 45 OFF D 46 OFF E 47 OFF F unit Example : unit 47 : Set 4-1 to "OFF",4-2 to "", Rotary to "F" 4-1 4-2 Rotary SW 48 0 49 1 50 2 51 3 52 4 53 5 54 6 55 7 56 8 57 9 58 A 59 B 60 C 61 D 62 E 63 F 1 2 3 4 4 - (06-61) -
6-5-4. INFRARED ADDRESS SETTING A wireless remote controller (UTB- VB) is required to set the infrared. This function is available in all indoor unit with infrared signal receiver. Infrared for duct type models can be made possible by using the optional IR receiver unit (UTB- WA). Note : Since Beeping sound generate from indoor unit PCB installed far away (not from IR Receiver unit), sound might not be heard. The indoor unit s refrigerant and indoor unit can be set using the infrared. When remote controller is required, set by the rotary switch on the indoor unit s PCB. PREPARATI FOR INFRARED ADDRESS SETTING (1) Set the switch on the indoor unit s PCB that is used for manual is set to 00 at factory. (This process is unnecessary for newly installed and not yet set the SW.) CN22 CN21 CN23 CN24 CN27 SW10 SW3 SW4 SW5 SW1 SW2 1 2 3 4 5 80 6 7 1 2 3 4 5 80 6 7 SW1 SW2 SW3 SW4 SW5 CN11 JM2 JM1 CN10 1 2 3 4 "00" "00" Check the position "0" (Factory ) If it is set to any other numbers, that value will be enabled. (2) Turn on the power to the indoor unit. By turning on the power indoor units initializes EEV, so make sure the piping air-tight test and vacuuming have been conducted before turning on the power. Also check again to make sure no wiring mistakes were made before turning on the power. Breaker 20A units unit - (06-62) -
SWITCHING SELECTI OF ADDRESS SETTING MODE (3) Press and hold the MANUAL/AUTO button for 3 seconds. Pi Pi Pi (4) Press and hold the FAN CTROL and the + buttons. Whilst holding these 2 buttons, press the "ACL" button. OPERATI indicator (Red) LAMP IR RECEIVER UNIT MANUAL AUTO MANUAL AUTO FAN CTROL SET TEMP (+) ACL Address mode display The position of the MANUAL/AUTO button varies depending on the model. Refer to the operation manual for the position that is included with the unit. The error will be displayed by continuosly pressing the "MANUAL/AUTO" for 10 sec or more. In this case release the button or turn off the power. When the has already been set in the board, the operation LAMP will light up and the TIMER and s will display the number of. An explanation of the displayed information as shown below. As a Ceiling Wall type, LAMP color might be different. SELECTI AND CFIRMATI OF CUSTOM CODE (5) Press the + or - buttons to select the custom code that matches the with the indoor unit. By selecting the appropriate custom code, the communication between the indoor unit and the wireless RC become possible. CUSTOM CODE ( - - - ) The initial is " " (6) Press the VERTICAL AIRFLOW "button to send the code to the indoor unit. Correct code: A Wrong code: No Response Pi Pi - (06-63) -
BUTT NAME AND FUNCTI Refer to 6-5-2" for an outline of the. It does not matter whether the refrigerant or indoor unit is set first. (The method shown here sets the indoor unit first.) During mode, indoor unit reject the any operation command from remote controller. SLEEP button Confirmation of. Address data Address number * unit valid range 00-63 circut valid range 00-99 MASTER CTROL button - Start the mode - Changes the display digits Address code 01 --- unit 02 --- FAN MODE button Switches between the data (top line) and code (bottom line) START/STOP button Transmits "+" and "-" button Increases and decreases the displayed number IR RECEIVER UNIT Indication of code Indication of data number (1 degit) Indication of data number (10 degit) * IR Reciver unit is not shown for swing mark MANUAL/AUTO button Long push ----- Switches between the mode and (3 sec more) the complete mode. Short push ----- Switches the indicator display (between the indoor unit and refrigerant ) MANUAL AUTO Note : Address code display is as follows (operation lamp display) INDOOR UNIT ADDRESS DISPLAY REFRIGERANT CIRCUIT ADDRESS DISPLAY ADDRESS SETTING MODE OFF (Light continuously) OFF (Light 3 sec / 1 sec OFF) ADDRESS SETTING COMPLETE MODE OFF (Light OFF) OFF (Light 0.5 sec / 0.5 sec OFF) - (06-64) -
ADDRESS SETTING INDOOR UNIT ADDRESS SETTING (7) Press the MASTER CTROL button to access the mode. (8) Make sure the bottom number code is 01. If the number is other than 01, press the + or the - buttons to alter. SET "01" (9) Press the FAN CTROL button to access the data mode. The data will flash once this button is pressed. Address data (10) Press the + or the - buttons to adjust the data. The indoor unit range is between 00 and 63. Each time the master control button is pressed, it switches between 1 unit and 10 units positions. Range 00-63 Change degit + : UP - : DOWN (11) Press the START/STOP button once to send the information. A beeping noise will be heard if the command is accepted. Pi Pi Pi PiPiPi (12) unit will display the indoor unit data number on "TIMER " and "SWING " light. OPERATI TIMER continuously Flashing times of numbers (1 degit) (Example) ADDRESS : 34 SWING Flashing times of numbers (10 degit) In the following cases the signal is not read and a buzzer sounds. The indoor unit No. is set out of range (64 or more) : Pi Pi Pi (3 sec) 4 times 3 times The of the rotary switch on the PCB is not "00" : Pi Pi Pi Pi Pi ADDRESS 0 will not indicate. CHECK ADDRESS SETTING (13) Press the SLEEP button. PiPi CORRECT : Pi PiPi WRG: Pi PiPiPiPiPi (3 sec) - (06-65) -
REFRIGERANT CIRCUIT ADDRESS SETTING Note : The refrigerant can also be set evenwhile above indoor unit display. (14) Press the FAN CTROL button to select the code. (15) Press the "+" or "-" button to adjust code 02. Address code SET "02" (16) Press the FAN CTROL button to access the data mode. The data will flash once this button is pressed. Address data (17) Press the + or the - buttons to adjust the data. The refrigerant range is between 00 and 99. Each time the "master control " button is pressed, it switches between 1 unit and 10 units positions. Range 00-99 Change digit + : UP - : DOWN (18) Press the START/STOP button once to send the information. A beeping noise will be heard if the command is accepted. Pi Pi Pi PiPiPi (19) unit will display the refrigerant data number on "TIMER " and "SWING " light. OPERATI 3 sec 1 sec OFF (Example) ADDRESS : 25 TIMER Flashing times of numbers (1 degit) SWING Flashing times of numbers (10 degit) In the following cases the signal is not read and a buzzer sounds. The of the rotary switch on the PCB is not "00" : Pi Pi Pi Pi Pi 5 times 2 times ADDRESS 0 will not indicate and. ADDRESS display will automatically switched from indoor unit to refrigerant. CHECK ADDRESS SETTING (20) Press the SLEEP button. PiPi CORRECT : Pi PiPi WRG: Pi PiPiPiPiPi (3 sec) - (06-66) -
DISPLAY ADDRESS CODE SWITCHING (21) Address display switches between indoor unit and refrigerant by pressing "MANUAL/AUTO " button once shortly. OPERATI LAMP (Red) Pi unit : 4 times 3 times MANUAL AUTO : 3 sec / 1 sec OFF IR RECEIVER UNIT MANUAL AUTO 5 times 2 times Check to make sure the is correct. COMPLETI OF ADDRESS SETTING MODE (22) Press and hold the MANUAL/AUTO button for 3 seconds. Pi Pi Pi IR RECEIVER UNIT OPERATI LAMP (Red) * Operation lamp change displays MANUAL AUTO Timer lamp keep blinks the number of times of No. (23) Press the ACL button. After pressing the ACL button, please set the custom code again if b,c,d. The signal is not received afer switched completion mode. (Pi Pi Pi Pi Pi) Press the "MANUAL/AUTO MANUAL AUTO " button again for 3 sec to return to if required to return the mode. ACL (24) Press MANUAL/AUTO button shortly to select the both to be checked correct OPERATI LAMP (Red) unit : OFF 4 times 3 times IR RECEIVER UNIT MANUAL AUTO MANUAL AUTO Check to make sure the is correct. : 0.5 sec / 0.5 sec OFF 5 times 2 times - (06-67) -